The 3120-N…-…T1-… thermal circuit breaker/switch combination unites overcurrent protection and the function of an ON/OFF switch within a single component. The trip element is a thermal bimetal.
Type 3120-N…-…T1-… is ideally suited for overload protection of motors, pumps, transformers and cables. After tripping, it can reliably, easily and quickly be reset. The positively trip-free mechanism ensures reliable disconnection of the circuit even with the actuator blocked.
Type 3120-N is also available with thermal-magnetic trip: Typ 3120-N…-…M1-…
Type 3120-N is also available as a switch in accordance IEC/EN 61058 (see data sheet switch only) and with X3120 Power Entry Module.
Voltage rating |
|
---|---|
Current ratings | from 0.1 A up to 20 A (up to 30 A to special order, single pole only) |
Number of poles | double pole single pole |
Mounting method | flange |
Terminal design | blade terminals screw terminals |
Actuation | push button rocker |
Water splash protection | with water splash protection without water splash protection |
Illumination | with illumination without illumination |
Typical life | single pole AC 240 V: 0,1…20 A 30 000 operations at 1 x IN, inductiveDC 50 V: 0,1…4 A 30 000 operations at 1 x IN, inductive 4,5…16 A 30 000 operations at 1 x IN, resistiveDC 28 V: 0,1…20 A 30 000 operations at 1 x IN, inductive double pole DC 50 V: |
Interrupting capacity Icn | (IEC/EN 60934) 1, 2-pole: IN 0,1 … 2 A, UN AC 240 V / DC 50 V, Icn 10 x IN 1-pole: IN 2,5 … 10 A, UN DC 50 V, Icn 50 A 1-pole: IN 2,5 … 20 A, UN AC 240 V / DC 28 V, Icn 200 A 2-pole: IN 2,5 … 20 A, UN DC 50 V, Icn 250 A 2-pole: IN 2,5 … 20 A, UN AC 240 V / DC 28 V, Icn 300 A |
Certificates | VDE, UL, CSA, CCC, KC |
Order number | Description | |
---|---|---|
Y30386201 | terminal adapter | ![]() |
Y30427501 | Cover for terminal area (IP 20) | ![]() |
Y30367502 | spacer for -F3/N3…
panel thickness < 4 mm |
![]() |
Y30367601 | spacer for -F5/N5… | ![]() |
Y31214001 | plug-in connector | ![]() |