XAR6

XAR6

AR6 Fitered unregulated power supply input 12-24Vac / output 12-24Vdc max.6A
Powered by a 12-24 Vac secondary transformer
Rail mountable

Series with not stabilized output
Code XAR6
Type AR6
HS code 85044083
INPUT TECHNICAL DATA
Input rated voltage 12-24 Vac
Input voltage AC 6…20 Vac
Frequency 47…63 Hz
Current consumption 7.2 A (24 Vac)
Internal protection fuse T 8 A
External protection on AC line MT: C-10 A / Fuse: T 10 A
OUTPUT TECHNICAL DATA
Output voltage range Uout = (Uin x 1.41) – 2V
Continuous current 6 A at 20°C
Overload limiting External fuse must be installed
Ripple @ nominal ratings 2.5 Vpp
Hold up time >20 ms
Status indication LED „DC OK“
GENERAL TECHNICAL DATA
Operating temperature range –20…+45°C
Input / output isolation not insulated
Input / ground isolation 0.5 kVac / 60 s
Alarm contact no
Output / ground isolation 0.5 kVac / 60 s
Parallel connection no
Protection degree IP 00
Overvoltage category / pollution degree II / 2
Connection terminal 2.5 mm² / 2.5 mm²
Housing material UL94V-0 plastic material
Dimensions (LxHxD) 70x80x93 mm
Approximate weight 140 g
Mounting information vertical on a rail, 20 mm from adjacent components
ACCESSORIES
Mounting rail (IEC60715/TH35-7.5) PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB
APPROVALS AND MARKINGS
LOGO_CE.png

Dokumenty ke stažení

Produktová stránka