XCSA120CC

XCSA120CC

CSA120CC DC/DC converter 24Vdc/ 24Vdc 5A
DC wide range input
Short circuit, overload, input and output overvoltage protections
Over temperature protection
Compact dimension

Code XCSA120CC
Type CSA120CC
HS code 85044083
INPUT TECHNICAL DATA
Input rated voltage 24 Vdc
Input voltage DC 18…36 Vdc
Current consumption 5.8 A (24 Vdc) ±10%
Inrush peak current 90 A
Internal protection fuse T 10 A
External protection on AC line MT: C-13 A / Fuse: T-13 A
OUTPUT TECHNICAL DATA
Output voltage range 24 Vdc
Output adjustable range 22.5…27.5 Vdc
Continuous current 5 A (24 Vdc)
Overload limiting 6.5 A
Short circuit peak current 12 A for 300 ms
Ripple @ nominal ratings 150 mVpp
Hold up time 2 ms
Status indication LED „DC OK“
Parallel connection possible
Redundant parallel connection possible with external ORing diode
GENERAL TECHNICAL DATA
Efficiency 87% (24 Vdc)
Dissipated power 18 W (24 Vdc)
Operating temperature range –20…+50°C
Input / output isolation 2.1 kVdc / 60s
Input / ground isolation 1.41 kVdc / 60s
Output / ground isolation 0.75 kVdc / 60s
Standard / approvals EN 60950-1
EMC Standard EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4
Overvoltage category / pollution degree II / 2
Protection degree IP 20
Connection terminal 2.5 mm² / 2.5 mm²
Housing material aluminium
Dimensions (LxHxD) 40x130x115 mm
Approximate weight 550 g
Mounting information vertical on a rail, 10 mm from adjacent components
Alarm contact no
ACCESSORIES
Mounting rail (IEC60715/TH35-7.5) PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB
Mounting rail (IEC60715/TH35-15) PR/3/PP, PR/3/PP/ZB, PR/3/PA, PR/3/PA/ZB
APPROVALS AND MARKINGS
LOGO_CE.png

Dokumenty ke stažení

Produktová stránka