XCSD1015W024VAA

XCSD1015W024VAA

CSD1-015W/024V/AA Single phase power supply input 120-230Vac / output 24Vdc 0.6A
Single phase and DC input
Short circuit, overload, input and output overvoltage protections
Over temperature protection
Suitable for standard applications
Isolation Class 2, no grounding needed

Series Domotic Power
Code XCSD1015W024VAA
Type CSD1-015W/024V/AA
HS code 85044083
INPUT TECHNICAL DATA
Input rated voltage 120–230 Vac
Input voltage AC 85…264 Vac
Input voltage DC 100…370 Vdc (derating Uin
Frequency 47…63 Hz
Current consumption 0.29 A (120 Vac) / 0.18 A (230 Vac)
Inrush peak current 5 A
Power factor > 0.6
Internal protection fuse T 1 A
External protection on AC line MT: C-2 A / Fuse: T-2 A
OUTPUT TECHNICAL DATA
Output voltage range 24 Vdc ±1%
Continuous current 0.6 A at 60°C
Overload limiting 0.81 A
Ripple @ nominal ratings 50 mVpp
Hold up time 12 ms (120 Vac) / 20 ms (230 Vac)
Status indication LED „DC OK“
Parallel connection possible
Redundant parallel connection possible with external ORing diode
GENERAL TECHNICAL DATA
Efficiency 86% (120 Vac) / 86% (230 Vac)
Dissipated power 2.2 W (120 Vac) / 2.2 W (230 Vac)
Operating temperature range –20…+70°C (derating -0.9 W >60°C)
Input / output isolation 3 KVac / 60 s (SELV output)
Input / ground isolation class 2, without PE link
Output / ground isolation class 2 without PE connection
Standard / approvals EN 60950-1, EN 62368-1
EMC Standard EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4
Overvoltage category / pollution degree II / 2
Protection degree IP 20
Connection terminal 2.5 mm² / 2.5 mm²
Housing material UL94V-0 plastic material
Dimensions (LxHxD) 35x62x90 mm
Approximate weight 91 g
Mounting information vertical on a rail, 10 mm from adjacent components
ACCESSORIES
Alarm contact no
Mounting rail (IEC60715/TH35-7.5) PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB
Mounting rail (IEC60715/TH35-15) PR/3/PP, PR/3/PP/ZB, PR/3/PA, PR/3/PA/ZB
APPROVALS AND MARKINGS
CURUS.png

Dokumenty ke stažení

Produktová stránka