XCSL1120W024VAA

XCSL1120W024VAA

CSL1-120W/024V/AA Single-phase power supply input 120-230Vac / output 24Vdc 5A
Single phase and DC input
Short circuit, overload, input and output overvoltage protections
Over temperature protection
Suitable for standard applications
Alarm contact

Series Easy Power
Code XCSL1120W024VAA
Type CSL1-120W/024V/AA
HS code 85044083
INPUT TECHNICAL DATA
Input rated voltage 120–230 Vac
Input voltage AC 85…264 Vac
Input voltage DC 100…370 Vdc (derating Uin
Frequency 47…63 Hz
Current consumption 1.5 A (120 Vac) / 0.8 A (230 Vac)
Inrush peak current 20 A
Power factor > 0.65
Internal protection fuse T 3.15 A
External protection on AC line MT: C-4 A / Fuse: T 4 A
OUTPUT TECHNICAL DATA
Output voltage range 24 Vdc ±1%
Output adjustable range 16 … 28 Vdc
Continuous current 5 A
Overload limiting >6.2 A for >30 s
Short circuit peak current 15 A for 50 ms
Ripple @ nominal ratings 50 mVpp
Hold up time 20 ms (120 Vac) / 20 ms (230 Vac)
Status indication LED „DC OK“
Alarm contact dry contact, max. 1A
Parallel connection possible
Redundant parallel connection possible with external ORing diode
GENERAL TECHNICAL DATA
Efficiency 85% (120 Vac) / 85% (230 Vac)
Dissipated power 21.2 W (120 Vac) / 21.2 W (230 Vac)
Operating temperature range –20…+70°C (derating -3 W/°C >50°C)
Input / output isolation 3 KVac / 60 s (SELV output)
Input / ground isolation 1.5 kVac / 60 s
Output / ground isolation 0.5 kVac / 60 s
Standard / approvals EN 62368-1
EMC Standard EN 61000-6-2, EN 61000-6-4
Overvoltage category / pollution degree II / 2
Protection degree IP 20
Connection terminal 2.5 mm² / 2.5 mm²
Housing material aluminium
Dimensions (LxHxD) 40x115x115 mm
Approximate weight 400 g
Mounting information vertical on a rail, 20 mm from adjacent components
ACCESSORIES
Mounting rail (IEC60715/TH35-7.5) PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB
APPROVALS AND MARKINGS
CURUS.png

Dokumenty ke stažení

Produktová stránka