XCSL3480W024VAB

XCSL3480W024VAB

CSL3-480W/024V/AB 3-phase power supply input 400-500Vac / output 24Vdc 20A with.communication.port
3-phase 400-500 Vac input
Short circuit, overload, input and output overvoltage protections
Over temperature protection
Alarm contact
High overload capability to ensure the protections selectivity and start-up of heavy loads

Series Easy Power
Code XCSL3480W024VAB
Type CSL3-480W/024V/AB (3)
HS code 85044083
INPUT TECHNICAL DATA
Input rated voltage 3x 400–500 Vac
Input voltage AC 340…550 Vac
Input voltage DC 500 – 600 Vdc
Frequency 47…63 Hz
Current consumption 0.8 A (400 Vac)
Inrush peak current 22 A
Power factor 0.76
External protection on AC line MT: C-4 A / Fuse: T-3.15 A
OUTPUT TECHNICAL DATA
Output voltage range 24 Vdc ±1%
Output adjustable range 20…28.5 Vdc
Continuous current 20 A at 50°C
Overload limiting 23 A (max. 25 A constant current)
Short circuit peak current 35A 400 ms On /800 ms Off (HICCUP mode)
Ripple @ nominal ratings 200 mVpp
Hold up time 10 ms (400 Vac)
Status indication LED „DC OK“, LED „Stand-by“
Alarm contact dry contact, max. 1A
Parallel connection possible
Redundant parallel connection possible with external ORing diode
GENERAL TECHNICAL DATA
Efficiency 90.5% (400 Vac)
Dissipated power 48 W (400 Vac)
Operating temperature range –20…+70°C (derating -14 W/°C >50°C)
Input / output isolation 3 KVac / 60 s (SELV output)
Input / ground isolation 1.5 kVac / 60 s
Output / ground isolation 0.5 kVac / 60 s
Standard / approvals EN 60950-1
EMC Standard EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4
Overvoltage category / pollution degree II / 2
Protection degree IP 20
Connection terminal 4 mm² / 4 mm²
Housing material aluminium
Dimensions (LxHxD) 80x170x127 mm
Approximate weight 1.5 kg
Mounting information vertical on a rail, 20 mm from adjacent components
ACCESSORIES
Mounting rail (IEC60715/TH35-7.5) PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB
APPROVALS AND MARKINGS
LOGO_CE.png

Dokumenty ke stažení