XCSL85C

XCSL85C

CSL85C Single-phase power supply input 120-230Vac / output 24Vdc 3.5A
Single phase input
Short circuit, overload, input and output overvoltage protections
Over temperature protection
Suitable for standard applications

Series Easy Power
Code XCSL85C
Type CSL85C (1)
HS code 8504403000
INPUT TECHNICAL DATA
Input rated voltage 120–230 Vac
Input voltage AC 90…264 Vac
Frequency 47…63 Hz
Current consumption 1.6A (120 Vac) / 0.9 A (230 Vac)
Inrush peak current 20 A
Power factor > 0.65
Internal protection fuse T 2 A
External protection on AC line MT: C-4 A / Fuse: T 4 A
OUTPUT TECHNICAL DATA
Output voltage range 24 Vdc ±1%
Output adjustable range 23…27.5 Vdc
Continuous current 3.5 A at 45°C
Overload limiting >5.5 A for >30 s
Short circuit peak current 9 A for 50 ms
Ripple @ nominal ratings 40 mVpp
Hold up time 20 ms (120 Vac) / 70 ms (230 Vac)
Status indication LED „DC OK“
Parallel connection possible
Redundant parallel connection possible with external ORing diode
GENERAL TECHNICAL DATA
Efficiency 86% (120 Vac) / 90% (230 Vac)
Dissipated power 14 W (120 Vac) / 10 W (230 Vac)
Operating temperature range –20…+60°C (derating -1.45 W >45°C)
Input / output isolation 3 KVac / 60 s (SELV output)
Input / ground isolation 1.5 kVac / 60 s
Output / ground isolation 0.5 kVac / 60 s
Standard / approvals EN 60950-1
EMC Standard EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4
Overvoltage category / pollution degree II / 2
Protection degree IP 20
Connection terminal 2.5 mm² / 2.5 mm²
Housing material aluminium
Dimensions (LxHxD) 40x130x115 mm
Approximate weight 400 g
Mounting information vertical on a rail, 10 mm from adjacent components
ACCESSORIES
Mounting rail (IEC60715/TH35-7.5) PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB
Alarm contact no
Mounting rail (IEC60715/TH35-15) PR/3/PP, PR/3/PP/ZB, PR/3/PA, PR/3/PA/ZB
APPROVALS AND MARKINGS
LOGO_CE.png

Dokumenty ke stažení

Produktová stránka